§ 2756. Spacing Between Bare Energized Parts and Adjacent Surfaces.  


Latest version.
  • Minimum spacing for bare conductors shall be in accordance with Table 2756, although greater spacing may be required by unusual atmospheric or other special conditions.
    Table 2756
    Minimum Spacing in Inches Between Bare Energized Parts
    and Adjacent Surfaces
     
    Voltage Outdoor Indoor
     
    Phase
    Phase
    Phase
    Phase
    Phase
    to
    to
    to
    to
    to
    Phase
    Ground
    Phase
    Ground
    Phase
    601
    3 1/2
    5
    3/4
    3/4
    750
    3 1/2
    5
    3/4
    3/4
    1200
    3 1/2
    5
    1 1/4
    1 1/4
    2500
    3 1/2
    5
    2
    2 1/2
    5000
    6
    7
    2 1/2
    4
    7500
    6
    7
    4
    5
    15000
    7
    12
    6
    7
    23000
    10
    15
    10
    15
    35000
    13
    18
    13
    18
    Above 35 KV
    .37/KV
    .455/KV
    36/KV
    .455/KV
    NOTES:
    (1) Spacings shown are minimum for energized parts to energized parts or energized parts to ground for elevations up to 3,300 feet above sea level. From 3,301 to 10,000 feet elevations, increase spacings by 10 percent, and above 10,000 feet elevation, increase spacings by 20 percent. For voltages above 230 KV, spacings shall be as required for the BIL of the system.
    (2) For intermediate values of system voltage, use next higher voltage in table.
    (Title 24, Part 3, Section 3-710-33.)