§ 66265.194. General Operating Requirements.
Latest version.
- (a) Hazardous wastes or treatment reagents shall not be placed in a tank system if they could cause the tank, its ancillary equipment, or the secondary containment system to rupture, leak, corrode, or otherwise fail.(b) The owner or operator shall use appropriate controls and practices to prevent spills and overflows from tank or secondary containment systems. These include at a minimum:(1) spill prevention controls (e.g., check valves, dry discount couplings);(2) overfill prevention controls (e.g., level sensing devices, high level alarms, automatic feed cutoff, or bypass to a standby tank); and(3) maintenance of sufficient freeboard in uncovered tanks to prevent overtopping by wave or wind action or by precipitation. Uncovered tanks shall be operated to ensure at least 60 centimeters (2 feet) of freeboard, unless the tank is equipped with a containment structure (e.g., dike or trench), a drainage control system or a diversion structure (e.g., standby tank) with a capacity that equals or exceeds the volume of the top 60 centimeters (2 feet) of the tank.(c) The owner or operator shall comply with the requirements of section 66265.196 if a leak or spill occurs in the tank system.(d) Transfer, treatment or storage of hazardous waste in tanks shall comply with section 66265.17(b).HISTORY1. New section filed 5-24-91; operative 7-1-91 (Register 91, No. 22).
Note
Note: Authority cited: Sections 208, 25150 and 25159, Health and Safety Code. Reference: Sections 25159 and 25159.5, Health and Safety Code; 40 CFR Section 265.194.