California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 7. General Industry Safety Orders |
Group 20. Flammable Liquids, Gases and Vapors |
Article 142. Industrial Plants |
§ 5549. Sources of Ignition.
Latest version.
- (a) Adequate precautions shall be taken to prevent the ignition of flammable vapors by open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; radiant heat; or other sources of ignition.(b) Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100oF (37.8oC), shall not be dispensed into containers unless the nozzle or fill pipe and container are electrically interconnected. This can be accomplished by maintaining metallic contact during filling, by a bond wire between them, or by other conductive path having an electrical resistance not greater than 106 ohms.(c) See Article 140 for electrical classifications.HISTORY1. Amendment of subsection (b) and new Note filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.