§ 5530. Scope.
Latest version.
- This article shall apply to areas where Class I liquids are stored or handled or where Class II or Class III liquids are stored or handled at a temperature above their flash points.For areas where Class II or Class III liquids only are stored or handled at a temperature below their flash points, the electrical equipment may be installed in accordance with the provisions of the California Electrical Safety Orders for ordinary locations; however, care shall be used in locating electrical apparatus to prevent hot metal from falling into open equipment.(a) All electrical equipment and wiring shall be of a type specified by and shall be installed in accordance with the California Electrical Safety Orders.(b) In the application of classified areas, a classified area shall not extend beyond an unpierced floor, wall, roof or other solid partition.(c) Where the provisions of this article require the installation of electrical equipment suitable for Class I, Division 1 or Division 2 locations, ordinary electrical equipment including switchgear may be used if installed in a room or enclosure which is maintained under positive pressure with respect to the classified area. Ventilation make-up air shall be uncontaminated by flammable vapors.(1) Pressurizing or purging of classified areas shall be in compliance with NFPA 496-1974.(d) The area classifications listed in Table FL-1 are based on the premise that the installation meets the applicable requirements of this section in all respects.(e) Extent of classified areas shall be as contained in Table FL-1. (Title 24, T8-5530)Table FL-1Class IExtent ofLocationDivisionClassified AreaIndoors equipment in-1Area within 5 feet of any edge of such equip-stalled in accordance withment, extending in all directions.5546(d) where flammablevapor-air mixtures may ex-ist under normal operations.2Area between 5 feet and 8 feet of any edge ofsuch equipment, extending in all directions.Also, area up to 3 feet above floor or gradelevel within 5 feet to 25 feet horizontallyfrom any edge of such equipment. [FNa1]Outdoor equipment of the1Area within 3 feet of any edge of such equip-type covered in 5546(d)ment, extending in all directions.where flammable vapor-air mixtures may exist un-der normal operations.2Area between 3 feet and 8 feet of any edge ofsuch equipment extending in all directions.Also, area up to 3 feet above floor or gradelevel within 3 feet to 10 feet horizontallyfrom any edge of such equipment.Tank -Aboveground (Un-derground, see 5574)Shell, Ends, or Roof and2Within 10 feet from shell, ends or roof oftankDike AreaArea inside dikes to level of top of dike.Vent1Within 5 feet of open end of vent, extendingin all directions.Floating Roof1Area above the roof and within the shell.Drum and Container Filling1Within 3 feet of vent and fill opening, exOutdoors, or Indoorstending in all directionswith Adequate Ventilation2Area between 3 feet and 5 feet from vent orfill opening, extending in all directions. Alsoup to 18 inches above floor or grade levelwithin a horizontal radius of 10 feet fromvent or fill opening.Pumps, Bleeders, With-drawal, Fittings, Metersand Similar DevicesIndoors2Within 5 feet of any edge of such devices ex-tending in all directions. Also up to 3 feetabove floor or grade level within 25 feet hor-izontally from any edge of such devices.Outdoors2Within 3 feet of any edge of such devices,extending in all directions. Also up to 18inches above grade level within 10 feet ho-rizontally from any edge of such devices.PitsWithout Mechanical1Entire area within pit if any part is within aVentilationwithin a Division 1 or 2 classified area.With Mechanical Vent-2Entire area within pit if any part is within alationDivision 1 or 2 classified area.Containing Valves, Fit-2Entire pit.tings or Piping, and NotWithin a Division 1 or 2Classified AreaDrainage Ditches, Separ-2Area up to 18 inches above ditch, separ-ators, Impounding Basinsator, or basin. Also up to 18 inches abovegrade within 15 feet horizontally from anyedge.[FNa1] The release of Class I liquids may generate vapors to the extent that the entire building, and possibly a zone surrounding it, should be considered a Class I, Division 2 location.HISTORY1. Articles 140-148 (Sections 5530-5629, not consecutive) filed 11-28-75; effective thirtieth day thereafter (Register 75, No. 48).2. Amendments filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
Note
Note: Authority cited: Section 142.3, Labor Code.