§ 5327. Intraline Separation of Operating Buildings.  


Latest version.
  • (a) All mass detonating explosives and pyrotechnic devices manufacturing buildings, including those where explosive charges are assembled, prepared, or loaded shall be separated from all other buildings, including magazines, within the confines of the manufacturing plant at a distance not less than those shown in the following table when buildings are BARRICADED. Note:Explosives not subject to mass detonation may be processed in buildings located in accordance with other intraline distance tables of recognized authority such as DOD or ATF Tables 55.219 and 55.222 through 55.224, with footnotes.
    (b) When a building or magazine containing explosives is not barricaded the intraline distances shown in the following Table shall be doubled.
    Intra Plant Distance Table For Use Only Within Confines of Explosives Manufacturing Plants
    Distance in
    Distance in
    Feet When
    Feet When
    Pounds
    Pounds
    Building is
    Pounds
    Pounds
    Building is
    Over
    Not Over
    Barricaded [FNa1]
    Over
    Not Over
    Barricaded [FNa1]
    2
    5
    16
    12,000
    14,000
    220
    5
    10
    20
    14,000
    16,000
    230
    10
    20
    25
    16,000
    18,000
    238
    20
    30
    28
    18,000
    20,000
    245
    30
    40
    31
    20,000
    25,000
    265
    40
    50
    34
    25,000
    30,000
    280
    50
    75
    38
    30,000
    35,000
    295
    75
    100
    42
    35,000
    40,000
    310
    100
    125
    45
    40,000
    45,000
    320
    125
    150
    48
    45,000
    50,000
    330
    150
    200
    53
    50,000
    55,000
    340
    200
    250
    57
    55,000
    60,000
    350
    250
    300
    60
    60,000
    65,000
    360
    300
    400
    66
    65,000
    70,000
    370
    400
    500
    71
    70,000
    75,000
    380
    500
    600
    76
    75,000
    80,000
    390
    600
    700
    80
    80,000
    85,000
    395
    700
    800
    84
    85,000
    90,000
    400
    800
    900
    87
    90,000
    95,000
    410
    900
    1,000
    90
    95,000
    100,000
    420
    1,000
    1,200
    96
    100,000
    110,000
    430
    1,200
    1,400
    101
    110,000
    120,000
    445
    1,400
    1,600
    106
    120,000
    130,000
    455
    1,600
    1,800
    110
    130,000
    140,000
    465
    1,800
    2,000
    113
    140,000
    150,000
    475
    2,000
    2,500
    122
    150,000
    160,000
    485
    2,500
    3,000
    130
    160,000
    170,000
    495
    3,000
    4,000
    143
    170,000
    180,000
    505
    4,000
    5,000
    154
    180,000
    190,000
    515
    5,000
    6,000
    164
    190,000
    200,000
    525
    6,000
    7,000
    172
    200,000
    210,000
    535
    7,000
    8,000
    180
    210,000
    230,000
    555
    8,000
    9,000
    190
    230,000
    250,000
    575
    9,000
    10,000
    200
    250,000
    275,000
    600
    10,000
    12,000
    210
    275,000
    300,000
    635
    [FNa1]
    When a building or magazine containing explosives is not barricaded, the distances shown in this Table should be doubled.
HISTORY
1. Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
2. Amendment of section and new Note filed 7-11-2003; operative 8-10-2003 (Register 2003, No. 28).

Note

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.