§ 2940.9. Protection from Backfeed Voltages.
Latest version.
- Before contacting the high voltage side of deenergized transformer(s), or conductor(s) connected thereto, all possible sources of backfeed shall be eliminated by:(a) disconnecting or grounding the high voltage side, or(b) disconnecting or short circuiting the low voltage side.Exception: System(s) worked as energized.HISTORY1. New section filed 2-22-88; operative 3-23-88 (Register 88, No. 9).2. Editorial correction of first paragraph (Register 95, No. 32).