California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 5. Electrical Safety Orders |
Group 2. High-Voltage Electrical Safety Orders |
Article 35. Workspace and Guarding |
§ 2934. Elevation of Unguarded Live Parts.
Latest version.
- Exposed energized parts above workspace and above areas where persons may normally walk or stand shall be maintained at elevations not less than that required by the following table:Table 2934 - Elevation of Unguarded Live Parts above WorkspaceNOMINAL VOLTAGEELEVATIONBETWEENPHASESFeetMeters601-75009.012.817501-35kV9.02.8Over 35kv9 feet + 0.37 inch/kv2.8 + 9.5 mm/kVabove 35kvover 35 kV1 The minimum elevation may be 8.5 ft. (2.6 m) for installations built before April 1, 2009.HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).3. Amendment of section and Note filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.