§ 2934. Elevation of Unguarded Live Parts.  


Latest version.
  • Exposed energized parts above workspace and above areas where persons may normally walk or stand shall be maintained at elevations not less than that required by the following table:
    Table 2934 - Elevation of Unguarded Live Parts above Workspace
    NOMINAL VOLTAGE
    ELEVATION
    BETWEENPHASES
    Feet
    Meters
    601-7500
    9.01
    2.81
    7501-35kV
    9.0
    2.8
    Over 35kv
    9 feet + 0.37 inch/kv
    2.8 + 9.5 mm/kV
    above 35kv
    over 35 kV
    1 The minimum elevation may be 8.5 ft. (2.6 m) for installations built before April 1, 2009.
HISTORY
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).
3. Amendment of section and Note filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).

Note

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.