California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 5. Electrical Safety Orders |
Group 2. High-Voltage Electrical Safety Orders |
Article 20. Interrupting and Isolating Devices |
§ 2852. Fault Closing Rating.
Latest version.
- Oil-filled cutouts shall have a fault closing rating equal to or greater than the available fault current which can occur at the cutout location, unless suitable interlocks or operating procedures preclude the possibility of closing into a fault.(Title 24, Part 3, Section 710-21(d)(4).)HISTORY1. Editorial correction adding NOTE filed 11-2-83 (Register 83, No. 45).2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.