California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 5. Electrical Safety Orders |
Group 2. High-Voltage Electrical Safety Orders |
Article 19. Outdoor Wiring |
§ 2831. Circuit Feedback.
Latest version.
- (a) Identification. Circuits shall be labeled at all accessible points with suitable warning signs stating the locations from which feedback may occur because of:(1) Circuits energized by manually or automatically operated equipment, or(2) Circuit configurations or connections, or(3) Circuits feeding a load which can be connected to auxiliary generating equipment, or(4) Circuits feeding synchronous motor-driven generator sets which can be energized by reverse power flow from batteries or other sources.(Title 24, Part 3, Section 3-710-89.)HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.