§ 2808. Roof Installations.
Latest version.
- Electrical equipment shall be permitted to be installed on the roof of a building, provided:(a) The building structure has sufficient strength to support the entire installation.(b) Where oil-insulated equipment is used, the roof shall be of two-hour, non-combustible fire resistive construction, and a curb high enough to contain the oil from the largest oil-filled equipment shall be provided. In no case shall the height of the curb be less than 6 inches. A drain shall be provided from the curbed enclosure to carry any oil which it may contain well away from the building.(Title 24, Part 3, Section 3-110-39.)HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.