§ 2795. Splices and Terminations.
Latest version.
- (a) Portable (Flexible) cables shall not be operated with splices unless the splices are of the permanent molded, vulcanized, or other approved type.(b) Terminations. Termination enclosures shall be suitably marked with a high voltage hazard warning, and terminations shall be accessible only to authorized and qualified personnel.HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Amendment filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).