§ 2790. Conductor Construction.  


Latest version.
  • Multiconductor portable cable for use in supplying power to portable or mobile equipment at over 600 volts, nominal, shall consist of No. 8 or larger conductors employing flexible stranding. However, the minimum size of the insulated ground-check conductor of Type G-GC cables shall be No. 10.
    Exception: Portable-type cable is not required to supply mobile equipment that is not frequently moved, provided the cable is suitably protected and will not be moved while energized.