§ 2773. Low-Voltage Wiring.


Latest version.
  • Secondary control devices and wiring which are provided as part of the metal-enclosed bus run shall be isolated by grounded metal barriers from all primary circuit elements with the exception of short lengths of wire, such as at instrument transformer terminals.
    (Title 24, Part 3, Section 364-30.)
HISTORY
1. Editorial correction filed 11-2-83 (Register 83, No. 45).

Note

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.