Latest version.
- Each bus run shall be provided with a permanent nameplate on which the following information shall be provided:(a) Rated voltage.(b) Rated continuous current; if bus is forced cooled, both the normal forced cooled rating and the self-cooled (not forced cooled) rating for the same temperature rise shall be given.(c) Rated frequency.(d) Rated impulse withstand voltage.(e) Rated 60-cycle withstand voltage (dry).(f) Rated momentary current.(g) Manufacturer's name and address.HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Editorial correction filed 11-3-83 (Register 83, No. 45).
Note
Note: Metal-enclosed buses shall be constructed and tested in accordance with ANSI C37.20 -1969.(Title 24, Part 3, Section 364-21.)Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.