California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 5. Electrical Safety Orders |
Group 2. High-Voltage Electrical Safety Orders |
Article 10. Conduit |
§ 2761. Rigid Metal Conduit.
Latest version.
- (a) Use. Rigid metal conduit shall be permitted to be used under all atmospheric conditions and occupancies, provided conduits and fittings exposed to the weather or to severe corrosive influences are of corrosion-resistant material or have coatings inside and outside suitable for the conditions. Where dissimilar metals are used, they shall be joined by an approved device or method.(Title 24, Part 3, Section 3-346-1.)(b) Running Threads. Running threads shall not be used.(Title 24, Part 3, Section 3-346-9(b).)(c) Support. Conduit shall be supported at least every 10 feet. However, rigid metallic runs of conduit made up with approved threaded couplings and uninterrupted by pull boxes shall be permitted to be secured in accordance with Table 2, provided such fastening prevents transmission of stresses to terminus when conduit is deflected between supports.Table 2761Maximum Distance BetweenConduit SizeConduit Supports1/2 inch10 feet3/4 inch10 feet1 inch12 feet1 1/4 inch14 feet1 1/2 inch14 feet2 inch16 feet2 1/2 inch16 feet3 inch and larger20 feet(Title 24, Part 3, Section 3-346-12.)HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.