California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 5. Electrical Safety Orders |
Group 1. Low-Voltage Electrical Safety Orders |
Article 9. Services |
§ 2380.1. Disconnecting Means.
Latest version.
- (a) Means shall be provided to disconnect all conductors in a building or other structure from the service-entrance conductors. The service disconnecting means shall plainly indicate whether it is in the open or closed position and shall be installed at a readily accessible location nearest the point of entrance of the service-entrance conductors.(b) Each service disconnecting means shall simultaneously disconnect all ungrounded conductors.(c) Each service disconnecting means shall be suitable for the prevailing conditions.HISTORY1. New article 9 (section 2380.1) and section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19). For prior history of article 9, see Register 79, No. 32.
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.