§ 2583.8. Cranes and Hoists.


Latest version.
  • (a) The conductive surfaces of cranes and hoists that enter the cell line working zone need not be grounded. The portion of an overhead crane or hoist that contacts an energized electrolytic cell or energized attachments shall be insulated from ground.
    (b) Remote crane or hoist controls that may introduce hazardous electrical conditions into the cell line working zone shall employ one or more of the following systems:
    (1) Isolated and ungrounded control circuit;
    (2) Nonconductive rope operator;
    (3) Pendant pushbutton with nonconductive supporting means and with nonconductive surfaces or ungrounded exposed conductive surfaces; or
    (4) Radio.