§ 2560.10. Clearances.


Latest version.
  • (a) Vertical and Horizontal. Signs and outline system enclosures shall have not less than the vertical and horizontal clearances from open conductors specified in the following table:
    TABLE 2560.10
    CLEARANCES
     
    Vertical clearance above all signs upon which persons can walk
     
    8 feet
    Vertical clearance above all signs upon which persons cannot walk
     
    3 feet
    Vertical clearance under signs
     
    3 feet
    Horizontal clearance from signs
     
    3 feet
     
    (Title 24, Part 3, Section 3-600-10(a).)
    (b) Elevation. The bottom of sign and outline lighting enclosures shall not be less than 16 feet above areas accessible to vehicles.
    Exception: The bottom of such enclosures may be less than 16 feet above areas accessible to vehicles where such enclosures are protected from physical damage.
    (Title 24, Part 3, Section 600-10(b).)