California Code of Regulations (Last Updated: August 6, 2014) |
Title 8. Industrial Relations |
Division 1. Department of Industrial Relations |
Chapter 4. Division of Industrial Safety |
Subchapter 5. Electrical Safety Orders |
Group 1. Low-Voltage Electrical Safety Orders |
Article 73. Electric Signs and Outline Lighting |
§ 2560.10. Clearances.
Latest version.
- (a) Vertical and Horizontal. Signs and outline system enclosures shall have not less than the vertical and horizontal clearances from open conductors specified in the following table:TABLE 2560.10CLEARANCESVertical clearance above all signs upon which persons can walk8 feetVertical clearance above all signs upon which persons cannot walk3 feetVertical clearance under signs3 feetHorizontal clearance from signs3 feet(Title 24, Part 3, Section 3-600-10(a).)(b) Elevation. The bottom of sign and outline lighting enclosures shall not be less than 16 feet above areas accessible to vehicles.Exception: The bottom of such enclosures may be less than 16 feet above areas accessible to vehicles where such enclosures are protected from physical damage.(Title 24, Part 3, Section 600-10(b).)HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Editorial correction of subsection (a) filed 11-3-83 (Register 83, No. 45).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.