§ 2553.19. Sizing of Feeder Conductors for Television Studio Sets.  


Latest version.
  • (a) General. It shall be permissible to apply the demand factors listed in Table 2553.19(a) to that portion of the maximum possible connected load for studio or stage set lighting for all permanently installed feeders between substations and stages and to all permanently installed subfeeders between the main stage switchboard and stage distribution centers or location boards.
    TABLE 2553.19(a)
    DEMAND FACTORS FOR STAGE SET LIGHTING
    Total Stage Set Lighting
    Feeder Demand
    Load (Wattage)
    Factors
     
    First 50,000 or less at
     
    100%
    Next 50,001 to 100,000 at
     
    75%
    Next 100,001 to 200,000 at
     
    60%
    All over 200,000
     
    50%
     
    (b) Portable Feeders. A demand factor of 50 percent of maximum possible connected load shall be permitted for all portable feeders.
    (Title 24, Part 3, Section 530-19.)