§ 2553.19. Sizing of Feeder Conductors for Television Studio Sets.
Latest version.
- (a) General. It shall be permissible to apply the demand factors listed in Table 2553.19(a) to that portion of the maximum possible connected load for studio or stage set lighting for all permanently installed feeders between substations and stages and to all permanently installed subfeeders between the main stage switchboard and stage distribution centers or location boards.TABLE 2553.19(a)DEMAND FACTORS FOR STAGE SET LIGHTINGTotal Stage Set LightingFeeder DemandLoad (Wattage)FactorsFirst 50,000 or less at100%Next 50,001 to 100,000 at75%Next 100,001 to 200,000 at60%All over 200,00050%(b) Portable Feeders. A demand factor of 50 percent of maximum possible connected load shall be permitted for all portable feeders.(Title 24, Part 3, Section 530-19.)HISTORY1. Editorial correction filed 11-2-83 (Register 83, No. 45).2. Amendment of Table 2553.19(a) filed 8-27-86; effective thirtieth day thereafter (Register 86, No. 37).