§ 2534.8. Disconnecting Means.


Latest version.
  • A disconnecting means shall be provided in each ungrounded conductor for each capacitor bank and shall meet the following requirements:
    (a) The disconnecting means shall open all ungrounded conductors simultaneously.
    (b) The disconnecting means shall be permitted to disconnect the capacitor from the line as a regular operating procedure.
    (c) The rating of the disconnecting means shall not be less than 135 percent of the rated current of the capacitor.
    Exception: A separate disconnecting means shall not be required where a capacitor is connected on the load side of a motor controller.