§ 2420.4. Conductor Supports.  


Latest version.
  • (a) Conductors smaller than No. 8 shall be rigidly supported on noncombustible, nonabsorbent insulating materials and may not contact any other objects. Supports shall be installed as follows:
    (1) Within 6 in. (152 mm) from a tap or splice;
    (2) Within 12 in. (305 mm) of a dead-end connection to a lampholder or receptacle; and
    (3) At intervals not exceeding 4.5 ft. (1.37 m), and at closer intervals sufficient to provide adequate support where likely to be disturbed.