§ 2390.20. Disconnecting Means for Fuses.  


Latest version.
  • A disconnecting means shall be provided on the supply side of all fuses in circuits over 150 volts to ground and cartridge fuses in circuits of any voltage where accessible to other than qualified persons so that each individual circuit containing fuses can be independently disconnected from the source of power. However, a current-limiting device without a disconnecting means is permitted on the supply side of the service disconnecting means. In addition, a single disconnecting means is permitted on the supply side of more than one set of fuses as permitted by the exception in Section 2530.112 for group operation of motors, and a single disconnecting means is permitted for fixed electric space-heating equipment.
HISTORY
1. New section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).

Note

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.