§ 1612.2. Power Line Safety (over 350 kv).
Latest version.
- The requirements of Section 1611.5 and Section 1612.1 apply to power lines over 350 kV except:(a) For power lines at or below 1000 kV, wherever the distance “20 feet” is specified, the distance “50 feet” shall be substituted; and(b) For power lines over 1000 kV, the minimum clearance distance shall be established by the utility owner/operator or registered professional engineer who is a qualified person with respect to electrical power transmission and distribution.HISTORY1. New section filed 7-7-2011; operative 7-7-2011. Exempt from OAL review pursuant to Labor Code section 142.3(a)(3) (Register 2011, No. 27).
Note
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.